Amendment status not verified — confirm the current text below against the official source.
(1) In the case of multi-storeyed buildings or colonies or domestic, commercial or industrial complexes, the licensee shall estimate the load as per the following norms: (i) For domestic loads 500 watt per 10 square metre of the [plinth area constructed] (ii) For commercial loads [1000 watt per 10 square metre of the plinth area constructed] (iii) For lift, water lifting pump, streetlight if any, corridor/campus lighting and other common facilities actual load shall be calculated separately (iv) For Industrial loads actual load required shall be calculated separately 1. Substituted by Kerala Electricity Supply (Amendment) Code, 2020. Prior to the substitution it reads "constructed area" 2. Substituted by Kerala Electricity Supply (Amendment) Code, 2020. Prior to the substitution it reads "1500 watt per 10 square metre of the constructed area" (2) In the case of telecommunication tower on the top of multi-storeyed building, the load of such telecommunication tower shall be assessed separately.