Amendment status not verified — confirm the current text below against the official source.
The supply voltage levels for different connected loads or contract demands for new connections or for gross connected load or contract demand consequent to revision of connected load or contract demand, shall be as follows:Supply voltage Maximum connected load (for those without demand based metering) Maximum contract demand (for those with demand based metering) 240 V (single phase) 5 kW 415V (three phase) 100 kVA 100kVA 11 kV 3000 kVA 22kV 6000 kVA 33 kV 12000kVA 66 kV 20000kVA 110 kV 40000kVA 220 kV >40000 kVA Provided that the limit of connected load or contract demand specified for different supply voltage levels may be exceeded up to a maximum of twenty percent if supply at the appropriate higher voltage level is not feasible due to non-availability of distribution line at such higher voltage level in that area of supply: Provided further that the limits of connected load or contract demand specified for different supply voltage levels as specified above may be exceeded in exceptional cases with the approval of the Commission, subject to the conditions stipulated in such approval.