Section 6

Voltage levels for LT, HT and EHT supply.--

Amendment status not verified — confirm the current text below against the official source.

(1) Voltage levels specified for low tension (LT), high tension (HT) and extra high tension (EHT) supply are the following:-- (a) Low Tension (LT) supply,-- (i) Single phase 240 Volts between phase and neutral; (ii) Three phase 415 Volts between phases; (b) High Tension (HT) supply,-- (i) Three phase 11,000 Volts (11 kV) between phases; (ii) Three phase 22,000 Volts (22 kV) between phases; (iii) Three phase 33,000 Volts (33 kV) between phases; (c) Extra High Tension (EHT) supply,-- (i) Three phase 66,000 Volts (66 kV) between phases; (ii)Three phase 110,000 Volts (110 kV) between phases; (iii) Three phase 220,000 Volts (220 kV) between phases; (iv) Three phase 400,000 Volts (400 kV) between phases. (2) The licensee may, depending upon the technical conditions of the distribution system and subject to the approval of the Commission, give supply at a voltage and phase other than the classification of supply in sub-regulation (1) above.